High-energy soft starter FTR-K series

FEATURES

OVERVIEW

FTR-K series high-energy motor soft starter is customized according to user requirements and can meet the requirements of special environments and occasions such as high altitude, high temperature, low temperature, high humidity, marine salt spray, and vehicle-mounted. It has a wide range of voltage and capacity coverage. It is mainly used for the control of three-phase AC 50/60Hz ±5%, rated voltage 220V-1140V, and rated power 7.5kW-1000kW AC asynchronous motors. This product adopts reliable motor control technology and integrates functions such as motor starting, data acquisition and display, motor protection, and soft stopping into one. The simple Chinese and English liquid crystal display interface makes operation simpler and quicker. Users only need to connect an external molded case circuit breaker and contactor to meet the motor control requirements.

Basic Parameters: 

 Parameter/SpecificationDescription/Value
Voltage Drop (Without Bypass)2.5V per Thyristor 
Voltage Drop (With Bypass)  Total < 1V 
 Isolation Method Photoelectric isolation  
Kick Start Voltage, Time    40-100% Ue, 0.02-2.00S Adjustable
Ramp Initial Voltage, Time100-500% Ue, 1-200S Adjustable
Current Limit Value, Protection Time100-500%, 1-200S Adjustable
Soft Stop Voltage, Time  50-100% Ue, 1-30S Adjustable 
Start Overload Capability0-16 Levels 
Running Overload Capability 0-8 Levels
Over Load Protection Value800%, 1-10S Adjustable 
Unload Protection Value50%, 1-10S Adjustable 
Analog Input Signal   0-10V, 4-20mA, Control Accuracy 0.01A, 1 Channel
Analog Output Signal 4-20mA, Current Resolution 0.02A, 1 Channel
Digital Input SignalActive Normally Open, Optocoupler Isolated, 1 Channel
Bypass Relay Output Contact Drive Capacity: AC250V 10A, DC30V 5A
Fault Relay OutputContact Drive Capacity: AC250V 5A, DC30V 5A
Programmable Relay Output Contact Drive Capacity: AC250V 5A, DC30V 5A, 2 Channels
Communication Interfaces2 Channels, Baud Rate 1200-38400 bps, 8 Data Bits, RS485, Supports Odd, Even, None Parity, 2 Stop Bits
 Communication Protocol Supports Modbus-RTU, H-Profibus-DP, Configurable Slave Address 1-128